HPE 3PAR StoreServ 10800-V800

End of life Date:
May 31, 2021
OEM:
HPE
Type:
Storage Device

Feature Description:-

2 m cabinet

Dimensions (W x H x D) 60 x 194.3 x 91.3 cm (23.6 x 76.5 x 36 in)

Service clearance (Front and back) Front/Rear: 91.4 cm (36 in) / 76.2 cm (30 in)

Weight (Not populated) 214.1 kg (472.1 lb)

Maximum weight (Fully populated) 870.8 kg ( 1,919.8 lb)

Maximum weight per leveling foot 217.7 kg (480 lb)

Maximum load per leveling foot 14 kg/sq cm (200 lb/sq in)

Component weights

10400 Base configuration1 314.7 kg (693.9 lb)

10800 Base configuration1 356.9 kg (786.9 lb)

2 controller nodes (Fully populated) 60.4 kg (133 lb)

Drive chassis (Fully populated) 81.6 kg (180 lb)

Service processor 9.4 kg (20.8 lb)

Supported host FC connections

FC connector type from storage system to host port LC to LC

FC cable core diameter OM3 / OM4

Connector boot length Standard

Electrical specifications

Feature Description

Single phase power supply requirements

Input voltage (V ac) 220 (200 - 240)

Frequency (Hz) 50 - 60

Circuit breaker maximum 30 A per Power Distribution Unit (PDU) (De-rated to 24 A)

Power connectors for 2 m cabinet (4) L6-30P with 1+1 redundant or (4) IEC 60309-32A (332P6S) with 1+1 redundant

Power receptacles (4) L6-30R with 1+1 redundant or (4) IEC 60309 with 1+1 redundant

Three phase power supply requirements[NEMA (North America, Taiwan, Philippines and Japan)]

Input voltage (V ac) 200 - 240 p-p

Frequency (Hz) 50 - 60

Circuit breaker maximum 48 A per PDU (De-rated to 27.71 A per phase)

Power connectors for 2 m cabinet (2) IEC 309, 3-pole, 4-wire, blue, ground clocked to 3:00 with 1+1 redundant

Power receptacles (2) Hubbell HBL460C9 W or equivalent

IEC (International)

Input voltage (V ac) 200 - 240 p-n; 380 - 415 p-p

Frequency (Hz) 50 - 60

Circuit breaker maximum 32 A per phase per PDU

Power connectors for 2 m cabinet (2) IEC 309, 4-pole, 5-wire, red, ground clocked to 6:00 with 1+1 redundant

Power receptacles (2) Hubbell C532C6S or equivalent

Maximum potential power draw per 2 m cabinet

Watts per cabinet 9,984 W and 34,075 BTU/hr

Actual power draw/heat dissipation

Service processor 350 W and 1,193 BTU/hr

Drive chassis (Without drive magazines) 200 W and 683 BTU/hr

Solid State Drive (SSD) and drive magazine Transactional (W / BTU/hr) - Under maximum load Idle (W / BTU/hr)

4 x 1920GB SSD / encryption drive magazine 32.4 / 110.55 8.8 / 30

4 x 300GB 15K SFF SAS drive magazine 39/132 34/117

4 x 600GB 15K SFF SAS/encryption drive magazine 29.2/100.4 28/96

4 x 450GB 10K SFF SAS/encryption drive magazine 27.2/92.8 22/75.1

4 x 600GB 10K SFF SAS/encryption drive magazine 29.6/100.8 25.2/84.4

4 x 1.2TB 10K SFF SAS drive magazine 32.8/111.6 24.8/84.4

4 x 1.8TB 10K SFF SAS drive magazine 30/102.4 29.2/99.2

4 x 2TB LFF SAS/encryption drive magazine 46.4/158 26.4/89.6

4 x 4TB LFF SAS/encryption drive magazine 52.4/178.4 36.4/124.4

4 x 6TB LFF SAS/encryption drive magazine 57.2/195 47.6/162.8

Controller node pair 1,315/4,487 990/3,378

Example full cabinet configuration (4 - Node 10400; 4 drive chassis, 160 600GB drives,1 service processor) 6,787/23,184 5,697/20,400

thomastech's unwavering commitment to quality, comprehensive solutions, and round-the-clock expertise transformed our Data Center journey." - John T.

We service all of your datacenter equipment
Servers. Storage. Network